BONDING (680-22) |
EACH OF THE
FOLLOWING ITEMS SHALL BE BONDED TOGETHER FORMING A
"BONDING GRID" IT IS NOT THE INTENT FOR THE BONDING
CONDUCTOR TO EXTEND TO ANY ELECTRODE, OR SERVICE
PANELBOARD | |
OK |
NA |
NC |
|
A-1 |
|
CONDUCTOR IS NO. 8 OR LARGER SOLID CU. CONDUCTOR INSULATED,
COVERED OR BARE |
|
|
|
|
A-2 |
|
METALLIC PARTS OF POOL STRUCTURE INCLUDING LADDERS AND
DIVING BOARD(S) |
|
|
|
|
A-3 |
|
CONCRETE REINFORCING STEEL (IF ANY EXIST) |
|
|
|
|
A-4 |
|
LIGHTING FIXTURES FORMING SHELL (IF ANY
EXIST) |
|
|
|
|
A-5 |
|
METAL FITTINGS 4" AND OVER IN ANY DIMENSION |
|
|
|
|
A-6 |
|
PUMP MOTORS, POOL COVER EQUIPMENT |
|
|
|
|
A-7 |
|
METAL-SHEATHED CABLES, RACEWAYS, PIPING WITHIN 5' OF POOL
HORIZONTALLY AND LESS THAN 12 ABOVE MAXIMUM
WATER. |
|
|
|
|
ITEM NO. |
GROUNDING (680-24 & 25) |
ALL OF THE
FOLLOWING EQUIPMENT SHALL BE GROUNDED WITH AN EQUIPMENT
GROUNDING CONDUCTOR | |
OK |
NA |
NC |
|
B-1 |
|
SIZED PER 250-122 MINIMUM 12 GA. CU. |
|
|
|
|
B-2 |
|
POOL LIGHTING FIXTURES AND RELATED EQUIPMENT |
|
|
|
|
B-3 |
|
PUMP AND OTHER POOL RELATED EQUIPMENT |
|
|
|
|
B-4 |
|
PANELBOARDS |
|
|
|
|
B-5 |
|
TRANSFORMER ENCLOSURES AND /OR JUNCTION BOXES |
|
|
|
|
ITEM NO. |
CONVENIENCE RECEPTACLES
(680-6) |
OK |
NA |
NC |
|
C-1 |
|
CONVENIENCE RECEPTACLE, 125V 15 OR 20 amp GFCI PROTECTED
|
|
|
|
|
C-2 |
|
LOCATED BETWEEN 10' AND 20' FROM THE INSIDE WALL OF THE
POOL AND LESS THAN 6'-6" ABOVE GRADE |
|
|
|
|
ITEM NO. |
PUMP OR MOTOR RECEPTACLES
(680-6) |
OK |
NA |
NC |
|
D-1 |
|
TWIST LOCK RECEPTACLE > 5' FROM INSIDE OF POOL AND GFCI
PROTECTED CIRCUIT |
|
|
|
|
D-2 |
|
STANDARD RECEPTACLE > 10' FROM INSIDE OF POOL AND GFCI
PROTECTED CIRCUIT |
|
|
|
|
ITEM NO. |
POOL MOTORS
(680-25(c)) |
OK |
NA |
NC |
|
E-1 |
GFCI
WIRING SUPPLYING PUMP MOTOR IS GFCI PROTECTED |
|
|
|
|
E-2 |
GROUNDING |
EQUIPMENT GROUNDING CONDUCTOR SIZED PER TABLE 250-122 BUT
NOT SMALLER THAN NO. 12 |
|
|
|
|
E-3 |
|
INSULATED COPPER CONDUCTOR (UF CABLE NOT
ACCEPTABLE) |
|
|
|
|
E-4 |
|
INSTALLED IN SAME CONDUIT AS CIRCUIT CONDUCTORS
|
|
|
|
|
E-5 |
CONDUIT OUTSIDE |
RIGID METAL CONDUIT, INTERMEDIATE METAL CONDUIT, RIGID
NONMETALLIC CONDUIT, OR TYPE MC CABLE LISTED FOR
APPLICATION |
|
|
|
|
E-6 |
CONDUIT |
ELECTRICAL METALLIC TUBING USED ON OR INSIDE A BUILDING
ONLY TO PROTECT CONDUCTORS |
|
|
|
|
E-7 |
FLEXIBILITY NECESSARY |
WHERE NECESSARY, LIQUIDTIGHT FLEXIBLE METAL OR NONMETALLIC
CONDUIT WITH APPROVED FITTINGS |
|
|
|
|
E-8 |
INTERIOR OF ONE FAMILY |
INTERIOR WIRING IN A ONE FAMILY STRUCTURE OR ACCESSORY
STRUCTURE MAY EMPLOY ANY WIRING METHOD RECOGNIZED BY NEC
CHAPTER 3 THAT CONTAINS A 12 GA COPPER EQUIPMENT GROUNDING
CONDUCTOR |
|
|
|
|
ITEM NO. |
LIGHTING FIXTURES/PADDLE
FANS (680-6(a)) |
OK |
NA |
NC |
|
F-1 |
NEW FIXTURES |
MINIMUM 12' VERTICALLY ABOVE MAXIMUM WATER LEVEL OR MORE
THAN 5' HORIZONTALLY FROM INSIDE WALL OF POOL |
|
|
|
|
F-2 |
EXISTING FIXTURES |
MINIMUM 5' VERTICALLY ABOVE POOL IF WITHIN 5' HORIZONTALLY
OF INSIDE WALLS OF POOL |
|
|
|
|
F-3 |
INDOOR POOLS |
LIGHTS ALLOWED WITHIN ABOVE DESCRIBED RESTRICTED AREA IF
ALL OF THE FOLLOWING ARE PROVIDED 1) LIGHT IS TOTALLY ENCLOSED
TYPE 2) GFCI PROTECTED AND 3) 7.5' ABOVE MAXIMUM WATER
LEVEL |
|
|
|
|
ITEM NO. |
DISCONNECTING
MEANS (680-12) |
OK |
NA |
NC |
|
G-1 |
|
DISCONNECTING MEANS PROVIDED LOCATED WITHIN 50' AND IN
SIGHT OF EQUIPMENT AND MINIMUM OF 5' FROM INSIDE WALL OF THE
POOL |
|
|
|
|
ITEM NO. |
UNDER WATER LIGHTING
FIXTURES (680-20) |
OK |
NA |
NC |
|
H-1 |
|
SUPPLY CIRCUITS 150 VOLTS OR LESS AND GFCI
PROTECTED |
|
|
|
|
H-2 |
|
TOP OF WALL MOUNTED FIXTURE LENS MINIMUM 18" BELOW NORMAL
WATER LEVEL |
|
|
|
|
H-3 |
|
TOP OF WALL MOUNTED FIXTURE LENSE MINIMUM 4" BELOW NORMAL
WATER LEVEL IF LISTED AND IDENTIFIED FOR USE AT THAT
LEVEL |
|
|
|
|
H-4 |
|
UPWARD FACING FIXTURE ADEQUATELY GUARDED |
|
|
|
|
H-5 |
|
FIXTURES THAT DEPEND ON SUBMERSION SHALL BE INHERENTLY
PROTECTED AGAINST HAZARDS OF OVERHEATING WHEN NOT
SUBMERGED |
|
|
|
|
H-6 |
WET-NICHE FIXTURE |
FORMING SHELL HAS PROVISIONS FOR CONDUIT ENTRIES AND
CONDUIT EXTENDS FROM FORMING SHELL TO SUITABLE JUNCTION BOX
(SEE 680-21) |
|
|
|
|
H-7 |
|
CONDUIT IS RIGID BRASS, INTERMEDIATE METAL, LIQUIDTIGHT
FLEXIBLE NONMETALLIC OR RIGID NONMETALLIC |
|
|
|
|
H-8 |
|
NO. 8 INSULATED COPPER CONDUCTOR IS INSTALLED IN
NONMETALLIC CONDUIT AND TERMINATED IN FORMING SHELL AND
JUNCTION BOX |
|
|
|
|
H-9 |
|
TERMINATIONS IN FORMING SHELL IS ENCAPSULATED IN A LISTED
POTTING COMPOUND |
|
|
|
|
H-10 |
|
END OF FLEXIBLE-CORD JACKED AND CONDUCTOR TERMINATIONS IN
FORMING SHELL INCLUDING GROUNDING CONNECTION IS ENCAPSULATED
IN A LISTED POTTING COMPOUND |
|
|
|
|
H-11 |
|
FIXTURE IS BONDED AND SECURED TO FORMING SHELL UNLESS
LISTED AND HAVING NO NONCURRENT CARRYING METAL
PARTS |
|
|
|
|
H-12 |
DRY-NICHE FIXTURE |
PROVIDED WITH PROVISIONS FOR DRAINAGE OF WATER AND
ACCOMMODATING ONE GROUND CONDUCTOR FOR EACH CONDUIT
ENTRY |
|
|
|
|
H-13 |
|
CONDUIT IS RIGID METAL CONDUIT, INTERMEDIATE METAL,
LIQUIDTIGHT FLEXIBLE NONMETALLIC OR RIGID NONMETALLIC BETWEEN
FIXTURE AND PANELBOARD |
|
|
|
|
H-14 |
|
JUNCTION BOX IF USED INSTALLED PER 680-21(a)
(5) |
|
|
|
|
H-15 |
NO-NICHE FIXTURE |
FIXTURE IS LISTED |
|
|
|
|
H-16 |
MOUNTING BRACKET HAS PROVISIONS FOR CONDUIT ENTRIES AND
CONDUIT EXTENDS FROM FORMING SHELL TO SUITABLE JUNCTION BOX
(SEE 680-21) |
|
|
|
|
H-17 |
CONDUIT IS RIGID BRASS, INTERMEDIATE METAL, LIQUIDTIGHT
FLEXIBLE NONMETALLIC OR RIGID NONMETALLIC |
|
|
|
|
H-19 |
NO. 8 INSULATED COPPER CONDUCTOR IS INSTALLED IN
NONMETALLIC CONDUIT AND TERMINATED IN MOUNTING BRACKET AND
JUNCTION BOX |
|
|
|
|
H-20 |
TERMINATIONS IN MOUNTING BRACKET ENCAPSULATED IN A LISTED
POTTING COMPOUND |
|
|
|
|
ITEM
NO. |
JUNCTION BOXES AND ENCLOSURES FOR TRANSFORMERS OR
GROUND-FAULT CIRCUIT INTERRUPTERS
(680-21) |
OK |
NA |
NC |
|
I-1 |
JUNCTION BOX |
LISTED AND LABELED FOR THE PURPOSE |
|
|
|
|
I-2 |
THREADED ENTRIES OR HUBS OR NONMETALLIC HUB LISTED FOR THE
PURPOSE |
|
|
|
|
I-3 |
COPPER, BRASS, SUITABLE PLASTIC, OR OTHER
CORROSION-RESISTANT MATERIAL |
|
|
|
|
I-4 |
ELECTRICAL CONTINUITY BETWEEN METAL CONDUIT AND GROUNDING
TERMINALS BY CORROSION-RESISTANT METAL INTEGRAL WITH THE
BOX |
|
|
|
|
I-5 |
INSIDE BOTTOM OF BOX IS 4 IN. ABOVE POOL DECK OR GROUND
LEVEL OR 8 IN. ABOVE MAXIMUM WATER LEVEL WHICHEVER PROVIDES
GREATER ELEVATION |
|
|
|
|
I-6 |
BOX IS LOCATED AT LEAST 4 FT. FROM INSIDE WALL OF
POOL |
|
|
|
|
I-7 |
LIGHTING SYSTEM IS OPERATING AT 15 VOLTS OR LESS--- A FLUSH
BOX IS USED MINIMUM OF 4 FT. FROM INSIDE WALL OF POOL AND
FILLED WITH APPROVED POTTING COMPOUND |
|
|
|
|
I-8 |
OTHER ENCLOSURES |
THREADED ENTRIES OR HUBS OR NONMETALLIC HUB LISTED FOR THE
PURPOSE |
|
|
|
|
I-9 |
PROVIDED WITH AN APPROVED SEAL (DUCT SEAL) AT CONDUIT
CONNECTION |
|
|
|
|
I-10 |
ELECTRICAL CONTINUITY BETWEEN METAL CONDUIT AND GROUNDING
TERMINALS BY CORROSION-RESISTANT METAL INTEGRAL WITH THE
BOX |
|
|
|
|
I-11 |
INSIDE BOTTOM OF BOX IS 4 IN. ABOVE POOL DECK OR GROUND
LEVEL OR 8 IN. ABOVE MAXIMUM WATER LEVEL WHICHEVER PROVIDES
GREATER ELEVATION |
|
|
|
|
I-12 |
BOX IS LOCATED AT LEAST 4 FT. FROM INSIDE WALL OF
POOL |
|
|
|
|
I-13 |
PROTECTION |
JUNCTION BOXES AND ENCLOSURES MOUNTED ABOVE GRADE NOT
LOCATED IN WALKWAY |
|
|
|
|
I-14 |
GROUNDING TERMINALS |
JUNCTION BOXES AND OTHER ENCLOSURES CONNECTED TO A CONDUIT
THAT EXTENDS DIRECTLY TO A FORMING SHELL OR MOUNTING BRACKET
IS PROVIDED WITH ONE MORE GROUNDING TERMINALS THAN CONDUIT
ENTRIES |
|
|
|
|
I-15 |
STRAIN RELIEF |
THE TERMINATION OF FLEXIBLE CORD OF AN UNDERWATER FIXTURE
IS PROVIDED WITH STRAIN RELIEF |
|
|
|
|
ITEM NO. |
CORD AND PLUG CONNECTED
EQUIPMENT |
OK |
NA |
NC |
|
J-1 |
|
ONLY USED ON STATIONERY EQUIPMENT RATED 20 AMPS OR
LESS |
|
|
|
|
J-2 |
|
AND NOT USED ON UNDER LIGHTING FIXTURE |
|
|
|
|
J-3 |
|
CORD IS NO LONGER THAN 3' ON OTHER THAN STORABLE
POOLS |
|
|
|
|
ITEM NO. |
OVER HEAD CONDUCTOR CLEARANCE |
OK |
NA |
NC |
|
K-1 |
|
ANY OVERHEAD CONDUCTORS COMPLY WITH CLEARANCE OF NEC 680-8
SEE FIGURE |
|
|
|
|
ITEM NO. |
UNDERGROUND WIRING LOCATION |
OK |
NA |
NC |
|
L-1 |
|
UNDERGROUND CONDUCTORS ARE NOT LOCATED UNDER THE POOL OR
WITHIN 5 FT. HORIZONTALLY FROM THE POOL WALL UNLESS NECESSARY
TO SUPPLY POOL EQUIPMENT |
|
|
|
|
ITEM NO. |
PANEL BOARD- WHICH SUPPLIES POOL EQUIPMENT |
OK |
NA |
NC |
|
M-1 |
|
REMOTE PANEL WITH AN INSULATED GROUNDING CONDUCTOR SIZED
PER 250-122 BUT NO SMALLER THAN NO. 12 INSTALLED WITH THE
FEEDER CONDUCTORS AND INSTALLED IN RIGID METAL CONDUIT,
INTERMEDIATE METAL CONDUIT, LIQUIDTIGHT FLEXIBLE NONMETALLIC
CONDUIT OR RIGID NONMETALLIC CONDUIT OR |
|
|
|
|
M-2 |
|
MAIN PANEL GROUNDED DIRECTLY PER NEC 250 OR PANEL IN AN
ACCESSORY STRUCTURE WITHOUT ANY METAL WATER LINE CONNECTING
BETWEEN THE TWO BUILDINGS |
|
|
|